Venation D series IoT gateway integrates multiple wired and wireless communication protocols. The embedded Web Configurator guides the device connection across brands or systems. The built-in innovative App Builder helps customize the control panels, scenes, dashboards according to field expertise that adds value to differentiate services.
Support standard DIN rail mounting
Integrate wired and wireless communication protocols
Easily integrate KNX, DALI, Modbus, DI, DO, Zigbee, Z-Wave, SNMP, MQTT protocols to achieve cross-brand and cross-system.
※Require the expansion product Venation E2.
Support Both Modbus Master and Slave simultaneously
Provides two Modbus/RTU Master interfaces, supports both 5 Modbus/TCP Master and 5 Modbus Slave.
Simultaneously compile Modbus and KNX summary tables
Various protocols can be converted into Modbus format and KNX group addresses and summarized into a clear table list.
Quickly diagnose data points and equipment
The built-in web configurator can immediately map the data points, diagnose and monitor the device. It improves installation efficiency.
Editable App Builder Tool
Provide a variety of device templates and panel components to customize exclusive control panels and dashboards App for different projects and various fields to increase the differentiation.
ardovenation remote App available in store
Download the ardoVenation Remote App and immediately use the customized App control panel and dashboard on your mobile phone.
LINE notification
Supports LINE push notifications, allowing users to get real-time reminders when the specified conditions change.
works with SCADA/BMS
Convert a variety of IoT communication protocols into Modbus data format to connect to SCADA or KNX to connect to PLC or BMS to provide high-quality operating efficiency.
Product Information
Item Dimension
Item weight
Power
- DC input 24V
- Power consumption less than 18.1W
- 2-Pin screw terminal block and DC Jack
Interface
- 1 x RJ45: 10M/100M Ethernet
- 1 x RS-232: D-Sub 9-pin female (DCE)
- 2 x isolated RS-485 (Modbus): 6-pin screw terminal blocks
- Thermal shutdown protection
- ESD protection with 12-KV HBM between Bus Pins and GND
- 1 x KNX: 2-pin red/black bus connection terminal
- 2 x DALI: 2-pin screw terminal blocks
- 1 x USB 2.0 Type-A connector
- 2 x 8-pin isolated Digital Input screw terminal blocks
- DI1.1/COM/DI1.2/COM/DI1.3/COM/DI1.4/COM
- DI2.1/COM/DI2.2/COM/DI2.3/COM/DI2.4/COM
- 2 x 6-pin isolated Digital Output screw terminal blocks
- PWR1/GND/DO1.1/DO1.2/DO1.3/DO1.4
- PWR2/GND/DO2.1/DO2.2/DO2.3/DO2.4
Operation environment
- Temperature: -20℃ to 45℃
- Humidity: 10%-95% (Non-condensing)
Connectivity
Modbus
Modbus TCP
- Support 5 Modbus Masters and 5 Modbus Slaves simultaneously
Modbus RTU
- 32 unit load (1/8 unit load: up to 256 nodes on a bus)
- Baud rate support from 4,800 to 30,400bps
KNX
- TP1, 9,600bps
- Up to 256 subscribers for one bus line
DALI
- Up to 64 addressable lighting devices per DALI line
- Auto detectable, auto addressing, individual lights diagnostic
- Bus topologies: Line, tree, star or any combination
- Cable lengths up to 300 meters (depending on cable cross-section)
- Transmission rate 1,200bps
Digital Input
- Wet-contact; input optical isolation 3750 Vrms
- Input logic “0” level: +-1V
- Input Logic “1” level: +-4 to +-30V
- Input Impedance: 3 K-Ohm
Digital Output
- Wet-contact; output optical isolation 3750 Vrms
- Output voltage range:5V to 30V
- Maximum tolerable current: 100mA
Model Name | Description | Model Number |
Venation D1 | Modbus/KNX/DALI/DIO | VD1B02AA00 |
Venation D1 | Modbus/KNX/DALI | VD1B05AA00 |
Venation D1 | Modbus/KNX | VD1B06AA00 |
Venation D1 | Modbus/DIO | VD1B08AA00 |
Keywords: IoT devices, IoT Gateway, IoT devices &sensors, Modbus, DI, DO, Digital Input, Digital Output, Read Coil, Read Discrete Coils, Read Holding Register, Modbus Registers, I/O, Conversion, PI R Sensor, Flood Detector,